Class C Din Rail PV Surge Protector

- Prosurge
- China
- Within 25 days
- 10kpcs per month
Type 2 surge arrester designed for low voltage DC system against surges at the boundaries from lightning protection zone 0B-2 and higher. In accordance with EN50539, IEC61643-11 and UL1449-5th. DC SPD for common mode protection. Pluggable module design, easy replacement. High discharge current 40kA 8/20. Reliable supervision due to disconnection device; Fault indication by red indication flag in window; With remote alarm terminal optional;
The PV40 V is class II (or T2 ) single pole PV DC SPD designed for DC application such as PV/ Photovoltaic system dc-side protection to against the damage from surge, at the boundaries from lightning protection zone 1-2 and higher..
With built in PROSURGE high energy MOV, PV40 V ensures remarkable surge current discharge capacity up to 40kA 8/20μs and high reliability. The unique design of thermal protection provides quick thermal re
sponse and secure disconnection.
Class II/T2 PV DC SPD per IEC/EN 61643-31 standard.
18mm narrow model design, Single pole SPD for multi-purpose surge protection, or prewired 2 poles or 3 poles
Application in Photovoltaic (PV) systems and other DC power system like charging system for electric vehicles etc.
Unique thermal disconnector design
Surge current capability up to 40kA 8/20μs
Low voltage protection level
Degradation failure indication and optional remote signal contact.
Pluggable module for easy replacement without the need to remove system wiring.
Wide operating temperature -40ºC ~85ºC
35mm DIN-rail mounting
Comply with EN 50539-11,UL1449 5th, IEEE C62.41,CSA C22.2 standards
l18mm narrow model design, Single pole SPD for multi-purpose surge protection
Part No. | PV40/48-V(-S) | PV40/75-V(-S) | PV40/100-V(-S) | PV40/150-V(-S) | PV40/200-V(-S) | PV40/300-V(-S) | PV40/400-V(-S) | PV40/500-V(-S) | PV40/600-V(-S) | PV40/750-V(-S) |
In accordance with | IEC/EN 61643-31; UL1449 5th; EN 50539-11 | |||||||||
Category IEC/EU/VDE | II /2/ C | |||||||||
Protection mode | DC+ to DC- or DC+/- to Ground | |||||||||
Nominal Voltage (DC) Un | 48V | 75V | 100V | 150V | 200V | 300V | 400V | 500V | 600V | 750V |
Max. continuous operating voltage (DC) Ucpv | 85V | 100V | 125V | 170V | 225V | 350V | 460V | 560V | 670V | 800V |
Nominal discharge current (8/20) In | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA |
Max. discharge current (8/20) Imax | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA |
Voltage protection level Up | 0.6kV | 0.6kV | 0.7kV | 0.8kV | 1.0kV | 1.2kV | 1.5kV | 2.0kV | 2.2kV | 2.5kV |
Response time tA | ≤25ns | |||||||||
Short-circuit Current Iscpv | 1000A | |||||||||
Operating temperature range | - 40ºC ~ + 85ºC | |||||||||
Altitude | -500m ~ +4000m | |||||||||
Cross-section of connection wire (max) | Single-strand 35mm2; multi-strand 25mm2 | |||||||||
Mounting | 35mm DIN-rail in accordance with EN 50022/DIN46277-3 | |||||||||
Enclosure material | thermoplastic; extinguishing degree UL94 V-0 | |||||||||
Degree of protection | IP20 | |||||||||
Installation width | 1 modules, DIN 43880 | |||||||||
Thermal disconnector | Internal Green – normal ; red - failure | |||||||||
Remote alarm contact | Optional | |||||||||
Approvals, Certifications | CE | |||||||||
Additional data for Remote Alarm Contacts | ||||||||||
Remote alarm contact type | Isolated Form C | |||||||||
Switching capability Un/In | AC: 250V/0.5A DC: 250V/0.1A; 125V/0.2A; 75V/0.5A | |||||||||
| Max. 1.5mm2(or # 16AWG) |
l18mm narrow model design, prewired two poles of V circuit for common mode protection
Part No. | PV40/48-V-C (-S) | PV40/75-V-C(-S) | PV40/100-V-C(-S) | PV40/150-V-C(-S) | PV40/200-V-C(-S) | PV40/300-V-C(-S) | PV40/400-V-C(-S) | PV40/500-V-C(-S) | PV40/600-V-C(-S) | |
In accordance with | IEC/EN 61643-31; UL1449 5th; EN 50539-11 | |||||||||
Category IEC/EU/VDE | II / 2/ C | |||||||||
Protection mode | DC+ to DC- , DC+/- to Ground | |||||||||
Nominal Voltage (DC) Un | 48V | 75V | 100V | 150V | 200V | 300V | 400V | 500V | 600V | |
Max. continuous operating voltage (DC) Ucpv | 85V | 100V | 125V | 170V | 225V | 350V | 460V | 560V | 670V | |
Nominal discharge current (8/20) In | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | |
Max. discharge current (8/20) Imax | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | |
Voltage protection level Up | DC+/- to PE | 0.6kV | 0.6kV | 0.7kV | 0.8kV | 1.0kV | 1.2kV | 1.5kV | 2.0kV | 2.2kV |
DC + to DC - | 1.0kV | 1.0kV | 1.2kV | 1.5kV | 2.0kV | 2.2kV | 2.8kV | 3.5kV | 4.0kV | |
Response time tA | ≤25ns | |||||||||
Short-circuit Current Iscpv | 1000A | |||||||||
Operating temperature range | - 40ºC ~ + 85ºC | |||||||||
Altitude | -500m ~ +4000m | |||||||||
Cross-section of connection wire (max) | Single-strand 35mm2; multi-strand 25mm2 | |||||||||
Mounting | 35mm DIN-rail in accordance with EN 50022/DIN46277-3 | |||||||||
Enclosure material | thermoplastic; extinguishing degree UL94 V-0 | |||||||||
Degree of protection | IP20 | |||||||||
Installation width | 2 modules, DIN 43880 | |||||||||
Thermal disconnector | Internal Green – normal ; red - failure | |||||||||
Remote alarm contact | Optional | |||||||||
Approvals, Certifications | CE | |||||||||
Additional data for Remote Alarm Contacts | ||||||||||
Remote alarm contact type | Isolated Form C | |||||||||
Switching capability Un/In | AC: 250V/0.5A DC: 250V/0.1A; 125V/0.2A; 75V/0.5A | |||||||||
| Max. 1.5mm2(or # 16AWG) |
l18mm narrow model design, prewired three poles of Y circuit for common mode & differential mode protection
Part No. | PV40/100-V-CD(-S) | PV40/200-V-CD(-S) | PV40/300-V-CD(-S) | PV40/400-V-CD(-S) | PV40/600-V-C(-S) | PV40/800-V-CD(-S) | PV40/1000-V-CD(-S) | PV40/1200-V-CD(-S) | PV40/1500-V-CD(-S) |
In accordance with | IEC/EN 61643-31; UL1449 5th; EN 50539-11 | ||||||||
Category IEC/EU/VDE | I+ II /1+2/ B+C | ||||||||
Protection mode | DC+ to DC- , DC+/- to Ground | ||||||||
Nominal Voltage (DC) Un | 100V | 200V | 300V | 400V | 600V | 800V | 1000V | 1200V | 1500V |
Max. continuous operating voltage (DC) Ucpv | 170V | 250V | 340V | 450V | 700V | 920V | 1120V | 1340V | 1500V |
Nominal discharge current (8/20) In | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA |
Max. discharge current (8/20) Imax | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA | 40kA |
Voltage protection level Up (DC+/- to PE, DC+ to DC-) | 1.0kV | 1.2kV | 1.5kV | 2.0kV | 2.2kV | 2.8kV | 3.5kV | 4.0kV | 4.5kV |
Response time tA | ≤25ns | ||||||||
Short-circuit Current Iscpv | 1000A | ||||||||
Operating temperature range | - 40ºC ~ + 85ºC | ||||||||
Altitude | -500m ~ +4000m | ||||||||
Cross-section of connection wire (max) | Single-strand 35mm2; multi-strand 25mm2 | ||||||||
Mounting | 35mm DIN-rail in accordance with EN 50022/DIN46277-3 | ||||||||
Enclosure material | thermoplastic; extinguishing degree UL94 V-0 | ||||||||
Degree of protection | IP20 | ||||||||
Installation width | 3 modules, DIN 43880 | ||||||||
Thermal disconnector | Internal Green – normal ; red - failure | ||||||||
Remote alarm contact | Optional | ||||||||
Approvals, Certifications | CE | ||||||||
Additional data for Remote Alarm Contacts | |||||||||
Remote alarm contact type | Isolated Form C | ||||||||
Switching capability Un/In | AC: 250V/0.5A DC: 250V/0.1A; 125V/0.2A; 75V/0.5A | ||||||||
| Max. 1.5mm2(or # 16AWG) |